The fault path
A chartplotter that resets when another load starts may have adequate battery voltage but insufficient voltage at its own terminals. Resistance in the supply or return path can produce a drop only when current flows. A no-load reading alone cannot rule out a poor connection.
The loaded measurement
- Identify the circuit and its rated operating range. Confirm the equipment manual, fuse, and system voltage. This procedure concerns low-voltage DC circuits; isolate shore power and AC work from the test.
- Run the affected equipment under a stable, representative load. Measure across the actual battery posts, then across the equipment’s positive and negative input terminals with the same load operating.
- Subtract the readings. The difference is the combined supply and return loss at that load. Record load state, both voltages, and the measured current if available.
- Locate the loss. A qualified technician can compare voltage across individual conductors or connections under load to find the segment causing the largest drop. De-energize before cleaning, tightening, or replacing parts; follow the component maker’s torque instructions.
Interpret and correct
Blue Sea Systems uses 3% allowable voltage drop for critical circuits such as electronics, navigation lights, bilge blowers, and panel feeders when sizing conductors; it lists 10% for selected noncritical loads. In the example above, 0.7 ÷ 12.6 is about 5.6%, above that 3% design target. This comparison is a screening clue, not a substitute for the equipment’s own voltage specification or a full circuit assessment.
Inspect the segment with the measured loss for corrosion, loose connections, poor crimps, undersized conductors, and excessive run length. Size a replacement using the round-trip length, current, installation environment, ampacity, and appropriate circuit protection. Do not increase a fuse rating to mask the fault.
If the battery-post voltage itself collapses under load, investigate the battery, charging system, and load separately. If battery voltage remains comparatively steady while voltage at the equipment falls, focus on the distribution path.
Blue Sea Systems: voltage drop and wire sizing · Choosing DC wire size · Victron Energy: wiring and voltage drop. The diagrams and worked numbers above are REFEVIA illustrations, not copied manufacturer figures.